Shower head MIN 300mm below top of enclosure?
« on: January 16, 2020, 07:37:54 PM »
Hi - I wondered if anyone here has wrestled with this issue and found a solution?

E3/AS1 3.3.3 states shower wall liners and enclosures must extend at least 300mm above the shower rose.

1800mm high kitset shower enclosures are very common in the market, and a compliant shower rose in one of these would need to be positioned no more than 1500mm above floor level to comply (300mm below the top of the enclosure and impervious liner.)

This is below chin height on an average adult and seems very impractical.

Every major NZ bathroom suppliers (as well as Mitre10/Bunnings etc) has in their literature, photos of completed shower enclosures with slide shower fittings that have the shower rose virtually at the top of the  enclosure, with paint finished walls above the liner.

Are all of these non-compliant, or is there another means of compliance for this type of installation?

Asking as I bought one of these enclosure sets to replace a very ugly 1970s shower base and cubicle, that a past owner has retrofitted with a nice modern mixer and slide shower. I would prefer not to touch any of the fixed plumbing, and just re-install all fittings over the new liner, as that would be a simple DIY project. But the head will be near the top of the liner and enclosure and according to 3.3.3 that isn't right.

Thank you very much for your time.
Regards
Rick

Linkback: https://www.plumbers.nz/q-and-a-baths-and-showers/64/shower-head-min-300mm-below-top-of-enclosure/2488/

Offline Plumber

  • Administrator
  • Hero Member
  • *****
  • Posts: 736
  • Karma: +52/-2
  • ***#1 Plumber***
Re: Shower head MIN 300mm below top of enclosure?
« Reply #1 on: January 17, 2020, 07:40:10 AM »
Based on the Internal moisture standards im guessing that as long as you prove that what is above the liner complies with the same standards you should be able to go higher. For example, wall above liner water proofed or maybe there is a paint finish that offers the same level of protection and compliance.

With tiled showers for example this is no issue. Would be interesting to know whether anyone has ever failed a council inspection because of this.

You could around this by replacing the "rose" with a rail and a spray.  ;D

Please note that the advice I am giving is only my opinion and not necessarily a fact.  Please refer to our terms and conditions.

Offline RRM

  • Newbie
  • *
  • Posts: 2
  • Karma: +0/-0
  • Im new @ Plumbers NZ!
Re: Shower head MIN 300mm below top of enclosure?
« Reply #2 on: January 19, 2020, 08:46:29 AM »
Thanks! After a bit more reading, according to 3.1.2 sheet lining with a gloss or semi gloss coating complies, so aqualine gib painted is fine.


Share via digg Share via facebook Share via linkedin Share via twitter

Similar Topics

  Subject / Started by Replies / Views Last post
xx
Low pressure shower head

Started by kerrbox

3 Replies
4986 Views
Last post October 18, 2011, 05:03:56 PM
by Zax
xx
unitec plumbing department head

Started by peasea

5 Replies
2926 Views
Last post March 12, 2013, 01:12:03 AM
by Smith Titos
xx
head pipe size? hot water pressure!!

Started by myles

7 Replies
4508 Views
Last post April 12, 2014, 10:56:28 PM
by myles
xx
Two shower heads in one shower

Started by gaz1

2 Replies
3975 Views
Last post August 22, 2010, 07:26:51 PM
by spud
 
Share this topic...
In a forum
(BBCode)
In a site/blog
(HTML)